Datasheet

CPS20.121
C-Series
12V, 30A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks
AC input range min. 85-264Vac continuous operation, no damage between 0 and 85Vac
min. 264-300Vac < 500ms
Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 84Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 33Vac steady-state value at 7.5A load, see Fig. 3-1
typ. 45Vac steady-state value at 15A load, see Fig. 3-1
typ. 62Vac steady-state value at 30A load, see Fig. 3-1
AC 100V AC 120V AC 230V
Input current typ. 4.0A 3.3A 1.8A at 12V, 30A, see Fig. 3-3
4.4A 3.7A 2.0A at 15V, 27A
Power factor
*)
typ. 0.99 0.99 0.95 at 12V, 30A, see Fig. 3-4
Crest factor
**)
typ. 1.5 1.5 1.65 at 12V, 30A
Start-up delay typ. 900ms 850ms 700ms see Fig. 3-2
Rise time typ. 72ms 72ms 72ms at 12V, 30A const. current
load, 0mF load capacitance,
see Fig. 3-2
typ. 120ms 120ms 120ms at 12V, 30A const. current
load, 30mF load capacitance,
see Fig. 3-2
Turn-on overshoot max. 200mV 200mV 200mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
4/26
300Vac264V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Apr. 2014 / Rev. 1.4 DS-CPS20.121-EN
All parameters are specified at 12V, 30A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.