Datasheet

CPS20.121
C-Series
12V, 30A, SINGLE PHASE INPUT
Fig. 3-3 Input current vs. output load at 12V Fig. 3-4 Power factor vs. output load at 12V
30A
0 3 6 9 1215182124
0
1
2
3
4
5A
Output Current at 12V
Input Current, typ.
27
a) 100Vac
b) 120Vac
c) 230Vac
b
a
c
Power Factor, typ.
Output Current at 12V
0 3 6 9 12 15 18 21 24 30A
0.75
0.8
0.85
0.9
0.95
1.0
27
a) 100Vac
b) 120Vac
c) 230Vac
a, b
c
4. DC-INPUT
Do not operate this power supply with DC-input voltage.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current
*)
max. 13A
peak
13A
peak
13A
peak
temperature independent
typ. 11A
peak
9A
peak
7A
peak
temperature independent
Inrush energy
*)
max. 2A
2
s 2.5A
2
s 0.5A
2
s temperature independent
*) Mains interruptions > 500ms
Fig. 5-1 Typical input inrush current
behaviour at nominal load and 25°C ambient
Input Current 5A / DIV
Input
230Vac
12Vdc
100mS/DIV
Output
Apr. 2014 / Rev. 1.4 DS-CPS20.121-EN
All parameters are specified at 12V, 30A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/26