Datasheet

CPS20.121
C-Series
12V, 30A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 12V
Adjustment range min. 12-15V guaranteed
max. 16.5V
*)
at clockwise end position of potentiometer
Factory settings typ. 12.0V ±0.2%, at full load, cold unit, in “single use” mode
typ. 12.0V ±0.2%, at full load, cold unit, in “parallel use” mode
typ. 12.5V at no load, cold unit, in “parallel use” mode
Line regulation max. 10mV 85-300Vac
Load regulation max. 100mV in “single use” mode: static value, 0A Æ 30A;
see Fig. 6-1
typ. 500mV in “parallel use” mode: static value, 0A Æ 30A,
see Fig. 6-2
Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 30A at 12V, see Fig. 6-1
nom. 27A at 15V, see Fig. 6-1
typ. 120A up to 15ms, output voltage stays above 10V, see Fig.
6-4, This peak current is available once every five
seconds. See chapter 22.1 for more peak current
measurements.
Output power nom. 360W at 12V
nom. 405W at 15V
Overload behaviour cont. current output voltage > 6Vdc, see Fig. 6-1
Hiccup
PLUS
mode
**)
output voltage < 6Vdc, see Fig. 6-1
Short-circuit current min. 35A
***)
load impedance <10mOhm, see Fig. 6-3
max. 42A
***)
load impedance <10mOhm, see Fig. 6-3
max. 12.6A
***)
average (R.M.S.) current, load impedance 25mOhm,
see Fig. 6-3
min. 120A up to 15ms, load impedance <10mOhm, see Fig. 6-4
typ. 130A up to 15ms, load impedance <10mOhm, see Fig. 6-4
Output capacitance typ. 5 600μF included inside the power supply
*) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 15.8V (in “single use” mode).
**) Hiccup
PLUS
Mode
At heavy overloads (when output voltage falls below 6V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the
overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3.
***) Discharge current of output capacitors is not included.
Apr. 2014 / Rev. 1.4 DS-CPS20.121-EN
All parameters are specified at 12V, 30A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/26