Manual

CPS20 Instruction Manual for Power Supplies
CPS20 Bedienungsanleitung für Stromversorgungen
Technical Data
1)
Technische Daten
1)
CPS20.241-D1
(DC/DC Converter)
CPS20.481-D1
(DC/DC Converter)
Output Voltage Ausgangsspannung nom. DC 24-28V DC 48-56V
Factory Setting at Full Load Werkseinstellung bei Nennlast “Single-Use”, typ. 24.1V 48.0V
Output Current continuous Ausgangsstrom dauernd nom. 20A at 24V
17.1A at 28V
10A at 48V
8.6A at 56V
Output Current PowerBoost
14)
Ausgangsstrom PowerBoost
14)
nom. 24A at 24V
20.6A at 28V
12A at 48V
10.3A at 56V
short-term (15ms) kurzzeitig (15ms) 80A 40A
Output Power continuous Ausgangsleistung dauernd nom. 480W 480W
Output Power PowerBoost
14)
Ausgangsleistung PowerBoost
14)
nom. 576W 576W
Output Ripple & Noise Voltage
13)
Ausgangswelligkeit
13)
max. 50mVpp 50mVpp
Output Overload Behavior Überlastverhalten am Ausgang - Hiccup
PLUS 17)
Hiccup
PLUS 17)
AC Input Voltage AC Eingangsspannung nom. not allowed/ nicht erlaubt not allowed/ nicht erlaubt
Input Frequency Eingangsfrequenz nom. - -
AC Input Current AC Eingangsstrom typ. - -
Power Factor Leistungsfaktor typ. - -
Allowed Voltage Input to Earth Erlaubte Spannung Eingang zu Erde max. 360Vdc
20)
360Vdc
20)
PFC Norm EN 61000-3-2 Class A PFC Norm EN 61000-3-2 Klasse A ---
DC Input Voltage DC Eingangsspannung nom. DC 110-300V ± 20%
15)
DC 110-300V ± 20%
15)
DC Input Current
3)
DC Eingangsstrom
3)
typ. 4.68 / 1.69A 4.68 / 1.69A
Slew Rate for voltage between Input
and Earth
Flankensteilheit der Spannung
zwischen Eingang und Erde
max. 1000V/µs 1000V/µs
Allowed Input Ripple Voltage Erlaubte Eingangswelligkeit max. 50Vpp (50Hz – 10kHz)
15Vpp (10kHz – 50kHz)
50Vpp (50Hz – 10kHz)
15Vpp (10kHz – 50kHz)
Input Inrush Current
3) 4)
Einschaltspitzenstrom
3) 4)
typ. 6A / 4A peak 6A / 4A peak
Hold-up Time
3)
Pufferzeit
3)
typ. 26ms / 26ms 26ms / 26ms
Efficiency
3)
Wirkungsgrad
3)
typ. 93.1% / 94.6% 93.1% / 94.6%
Power Losses
3)
Verlustleistung
3)
typ. 35.6W / 27.4W 35.6W / 27.4W
Operational Temperature Range
18)
Betriebstemperaturbereich
18)
nom. -25°C - +70°C -25°C - +70°C
Output Derating Leistungsrücknahme +60°C to +70°C 12W/°C 12W/°C
Storage Temperature Range Lagertemperaturbereich nom. -40°C - +85°C -40°C - +85°C
Humidity
5)
Feuchte
5)
IEC 60068-2-30 5 - 95% r.H. 5 - 95% r.H.
Vibration Schwingen IEC 60068-2-6 2g
16)
2g
16)
Shock Schocken IEC 60068-2-27 30g 6ms, 20g 11ms
16)
30g 6ms, 20g 11ms
16)
Degree of Pollution Verschmutzungsgrad IEC 62103 2
5) 19)
2
5) 19)
Degree of Protection Schutzart EN 60529 IP20 IP20
Class of Protection Schutzklasse IEC 61140 I
6)
I
6)
Over-temperature Protection Übertemperaturschutz OTP Yes / Ja Yes / Ja
Output Over-voltage Protection Überspannungsschutz am Ausgang OVP, max. 32Vdc 60Vdc
Return Voltage Resistance
8)
Rückspeisefestigkeit
8)
max. 35Vdc 63Vdc
Parallel Use
11)
Parallelschaltbar
11)
- Yes / Ja Yes / Ja
Serial Use
12)
Serienschaltbar
12)
- Yes / Ja Yes / Ja
Dimensions
9)
(WxHxD) Abmessungen
9)
(BxHxT) nom. 65x124x127mm 65x124x127mm
Weight Gewicht max. 940g, 2.1lb 940g, 2.1lb
Approvals Zulassungen - Æ 10) Æ 10)
Limited Warranty Eingeschränkte Gewährleistung Years / Jahre 3 3
1) All parameters are specified at 300Vdc input voltage, nominal output current, “Single Use”
setting, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
3) at 110Vdc / 300Vdc
4) Input inrush current is electronically limited, temperature independent and is valid for mains
interruptions > 500ms
5) Do not energize while condensation is present.
6) PE connection required (Ground).
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
9) Depth without DIN-rail.
10) See datasheet or markings on the unit.
11) Set jumper on the front to “Parallel Use”. A fuse (or diode) on the output is required if more
than three units are paralleled.
12) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
13) 50-Ohm measurement, bandwidth 20MHz
14) The PowerBoost is continuously allowed up to an ambient temperature of 45°C. Above 45°C,
do not use the PowerBoost longer than a duty cycle of 10% and/ or not longer than max. 1
minute every 10 minutes.
15) An output current derating might be necessary at input voltages below 100Vdc, see figure 7.
16) Higher levels possible when utilizing the wall mounting bracket ZM2.WALL
17) Hiccup
PLUS
is an overload behavior with a balanced power management. In normal mode it
provides generous power reserves but effectively protects connected equipment and cables
against damage in the event of failure. More details on the next pages.
18) The operational temperature range equals the surrounding air temperature measured 2cm
below the unit.
19) Caution: For use in a controlled environment according to CSA 22.2 No 107.1-01.
20) Provided, that the negative pole is grounded. If the positive pole is grounded, an additional
external fast-acting input fuse in the negative input is required (E.g. 8A KLKD fuse from
Littelfuse or a comparable UL listed fuse with the same ratings and characteristics. Otherwise
the status of the UL approvals becomes void.).
1) Alle Werte gelten bei 300Vdc Eingangsspannung, Nennausgangsstrom, „Single-Use“ Modus,
25°C Umgebung und nach einer Aufwärmzeit von 5 Minuten, falls nichts anderes angegeben.
3) bei 110Vdc / 300Vdc
4) Der Einschaltstromstoß ist elektronisch begrenzt, temperaturunabhängig und gilt für
Netzunterbrechungen > 500ms
5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils
rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene
10) Siehe Datenblatt oder Prüfzeichen auf dem Gerät.
11) Steckbrücke an der Front des Gerätes auf „Parallel Use“ umstellen. Bei mehr als drei Geräten
wird eine Sicherung oder eine Diode zur Entkopplung benötigt.
12) Nur für gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
13) 50-Ohm Messung, Bandbreite 20MHz
14) Der PowerBoost ist bis zu einer Umgebungstemperatur von +45°C dauerhaft erlaubt. Darüber
soll sie nicht länger als 10% (<1 Minute alle 10 Minuten) entnommen werden.
15) Unterhalb 100Vdc kann eine Leistungsrücknahme erforderlich sein. Siehe Bild 7.
16) Höhere Werte sind bei Verwendung des Wandmontageadapters ZM2.WALL möglich
17) Hiccup
PLUS
ist ein Überlastverhalten mit einem ausgewogenem Leistungsmanagement,
welches im Normalbetrieb kurzzeitig großzügige Leistungsreserven zur Verfügung stellt, aber
im Fehlerfall angeschlossene Verbraucher und Kabel effektiv vor Schäden schützt. Mehr
Informationen auf den nächsten Seiten.
18) Die Betriebstemperatur wird 2cm unterhalb des Geräts gemessen.
19) In Anwendungen nach CSA 22.2 No 107.1-01: Vorsicht - Verwendung nur in „controlled
environment“
20) Vorausgesetzt der neagtive Pol ist geerdet. Im Falle einer Erdung des positiven Pols ist eine
externe flinke Sicherung in der negativen Zuleitung erforderlich (z.B. 8A KLKD von Littelfuse
oder eine vergleichbare UL-gelistete Sicherung mit gleichen Nenndaten und Charakteristik,
ansonsten verliert die UL-Zulassung ihre Gültigkeit).