12V, 8A, TWO-PHASE INPUT
11. TERMINALS AND WIRING
Input Output
Type
screw terminals screw terminals
Solid wire 0.5-6mm
2
0.5-6mm
2
Stranded wire 0.5-4mm
2
0.5-4mm
2
American Wire Gauge 20-10 AWG 20-10 AWG
Wire stripping length 7mm / 0.275inch 7mm / 0.275inch
Screwdriver 3.5mm slotted or
Pozidrive No 2
3.5mm slotted or
Pozidrive No 2
Recommended tightening torque 0.8Nm, 7lb.in 0.8Nm, 7lb.in
Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed, but not required
12. RELIABILITY
AC 400V AC 480V
Lifetime expectancy
*) 51 000h 55 000h at 12V, 8A and 40°C
152 000h 147 000h at 12V, 4A and 40°C
144 000h 156 000h at 12V, 8A and 25°C
MTBF
**) SN 29500, IEC 61709 983 000h 967 000h at 12V, 8A and 40°C
1 799 000h 1 769 000h at 12V, 8A and 25°C
MTBF
**) MIL HDBK 217F 484 000h 455 000h at 12V, 8A and 40°C; Ground Benign GB40
636 000h 600 000h at 12V, 8A and 25°C; Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
Jan. 2010 / Rev. 1.0 DS-CT5.121-EN
All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.