Datasheet

CT5.121
C-Series
12V, 8A, TWO-PHASE INPUT
14. ENVIRONMENT
Operational temperature
*) -25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 14-1
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 2.5W/°C 60-70°C (140°F to 158°F)
Humidity **) 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock 30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 6000m (0 to 20 000ft) reduce output power or ambient temperature
above 2000m sea level.
Altitude de-rating 6W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 14-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
Fig. 14-1 Output current vs. ambient temp. Fig. 14-2 Output current vs. altitude at 12V
0
-25 0 20 40
70°C
1
3
4
5
6
8A
60
Ambient Temperature
c
o
n
t
i
n
u
o
u
s
2
7
Allowable Output Current at 12V
0
0 2000 4000
6000m
1
2
4
5
6
8A
Altitude
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
C
B
A
3
7
Allowable Output Current at 12V
Jan. 2010 / Rev. 1.0 DS-CT5.121-EN
All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/21