Datasheet

ML15.051
MiniLine
5V, 3A, SINGLE PHASE INPUT
22.8. OPERATION ON TWO PHASES
240V
+10%
max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
The power supply can also be used on two-phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying
voltage is below 240V+10%. Use a fuse or a circuit breaker to protect the
N input. The N input is internally not protected and is in this case
connected to a hot wire. Appropriate fuses or circuit breakers are specified
in section 22.3 “External Input Protection”.
22.9. USE WITHOUT PE ON THE INPUT
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2.
Please contact PULS if you do not plan to use the PE terminal. A different marking of the front foil is then required. In
such cases the PE terminal will change to an EMI ground terminal. Be aware that a connection to ground or earth of
this terminal must be done in the same manner as it would be a “real” PE terminal. (wire size, isolation, …)
Connecting this terminal can be beneficial to gain a high EMI immunity.
Symmetrical spikes or fast transients on the input side can be conducted directly to earth by the built-in filter
capacitors. The magnitude of such spikes or fast transients on the output side caused by the input is much smaller
compared to not connecting this terminal to ground.
Fig. 22-3 Earthed input Fig. 22-4 Not earthed input
Surge
19/21
Y
X
L
N
EMI-ground
Power Supply
+
-
Surge
X
L
N
Power Supply
+
-
Spike
24V
Oct. 2009 / Rev. 1.2 DS-ML15.051-EN
All parameters are specified at 5V, 3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany