Datasheet

ML60.121
MiniLine
12V, 4.5A, SINGLE PHASE INPUT
14. ENVIRONMENT
Operational temperature
*) -10°C to +70°C (14°F to 158°F) reduce output power according Fig. 14-1
Storage temperature -40°C to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 1.4W/°C 60-70°C (140°F to 158°F)
Humidity **) 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock 15g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating 4W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 14-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
Fig. 14-1 Output power vs. ambient temp. Fig. 14-2 Output power vs. altitude
0
-10 0 40
70°C
10
20
30
40
50
60W
60
Ambient Temperature
20
Allowable
Output Power
0
0 2000 4000
6000m
10
20
30
40
50
60W
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable
Output Power
15. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits *)
Output over-voltage protection typ. 18Vdc
max. 19Vdc
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. In such a
case, the output shuts down and stays down until the
input voltage is turned off and on again.
Output over-current protection electronically limited see Fig. 5-1
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 2.5mm in diameter e.g. screws, small parts
Over-temperature protection not included
Input transient protection MOV Metal Oxide Varistor
Internal input fuse T3.15A H.B.C. not user replaceable
*) In case of a protection event, audible noise may occur.
xxx. 201x / Rev. 1.1 DS--ML60.121-EN
All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/22