15. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. CE mark is in conformance with EMC guideline 89/336/EEC and
93/68/EEC and the low-voltage directive (LVD) 73/23/EWG. A detailed EMC Report is available upon request
EMC Immunity
EN 61000-6-1 EN 61000-6-2
Generic standards
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-1GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 L Æ N
N / L Æ PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ PE
500V
500V
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
Mains voltage dips EN 61000-4-11 70% of 100Vac
40% of 100Vac
40% of 100Vac
70Vac, 10ms
40Vac, 100ms
40Vac, 1000ms
Criterion A
Criterion C
Criterion C
Voltage interruptions EN 61000-4-11 0Vac, 5000ms Criterion C
Voltage sags SEMI F47 0200
96Vac, 1000ms
84Vac, 500ms
60Vac, 200ms
Criterion A
Criterion A
Criterion A
Input voltage swells PULS internal standard 300Vac, 500ms Criterion A
Powerful transients VDE 0160 over entire load
range
750V, 1.3ms Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply might shut-down and restarts by itself. No damages or hazards for the power supply occur.
EMC Emission
EN 61000-6-3 and EN 61000-6-4 Generic standards
Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines
EN 55022 Class A, output lines
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Fulfilled, active PFC
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequency
65 to 270kHz load and input voltage dependent