6. INPUT INRUSH CURRENT
An active inrush limitation circuitry limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first milliseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 6A
peak
7A
peak
13A
peak
-25°C to +70°C
typ. 4.5A
peak
5A
peak
10A
peak
-25°C to +70°C
Inrush energy
max. 2A
2
s 2A
2
s 2A
2
s -25°C to +70°C
Fig. 6-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
Input: 230Vac
Output: 24V, 3.4A
Ambient: 25°C
Upper curve: Input current 5A / DIV
Medium curve: Input voltage 500V / DIV
Lower curve: Output voltage 20V / DIV
Time basis: 100ms / DIV
7. DC-INPUT
DC input nom. DC 110-300V
DC input range min. 88-375Vdc continuous operation
DC input current typ. 0.8A / 0.29A 110Vdc / 300Vdc, 24V, 3.4A
Turn-on voltage typ. 61Vdc steady state value
Shut-down voltage typ. 47Vdc steady state value
Fig. 7-1 Wiring for DC Input
Fuse
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
Instructions for DC use:
a) Use a battery or similar DC source.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to a earth wire or
to the machine ground.
In case the –pole of the battery is not connected
to earth, use an appropriate fuse to protect the N
terminal.