12. TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field and factory wiring.
All terminals
Type
Quick-connect spring-clamp terminals
Solid wire Max. 6mm
2
Stranded wire Max. 4mm
2
American Wire Gauge Max. AWG10
Wire diameter Max. 2.8mm (including ferrules)
Wire stripping length Typ. 10mm / 0.4inch
Screwdriver Not applicable
Recommended tightening torque Not applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum
operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal
connection!
d) Do not use the unit without PE connection.
e) Ferrules are allowed.
1.
Insert the wire
2.
Snap the lever
To disconnect wire: same procedure
vice versa
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 27A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 12-2.
Fig. 12-1 Daisy chaining of outputs Fig. 12-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 27A
continuous!
11/27
All parameters are typical values specified at 24V, 20A, 3x 400Vac, 50Hz, symmetrical mains voltages, 25°C ambient and after
a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany