Datasheet

QT40.241
Q-Series
24V, 40A, THREE PHASE INPUT
Switching Frequencies
The power supply has three converters with three different switching frequencies
included. One is nearly constant. The others are variable.
Switching frequency 1 105kHz Resonant converter, nearly constant
Switching frequency 2 1kHz to 150kHz Boost converter, load dependent
Switching frequency 3 40kHz to 300kHz PFC converter, input voltage and load dependent
18. ENVIRONMENT
Operational temperature
*)
-25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 18-1
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 24W/°C 60-70°C (140°F to 158°F)
Humidity
**)
5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g
***)
2 hours / axis
IEC 60068-2-6
Shock 15g 6ms, 10g 11ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 18-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating 60W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 18-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. Curves and
figures for operation on only 2 legs of a 3-phase system can be found in chapter 26.4.
**) Do not energize while condensation is present.
***) Higher levels allowed when using the wall mounting bracket ZM2.WALL
Fig. 18-1 Output current vs. ambient temp. Fig. 18-2 Output current vs. altitude
Allowed Output Current at 24V
0
-25 0 20 40
70°C
10
20
30
40
50
60A
c
o
n
t
i
n
u
o
u
s
60
Ambient Temperature
s
h
o
r
t
-
t
e
r
m
(
4
s
)
Allowed Output Current at 24V
0
0 2000 4000
10
20
30
40
50
60A
c
o
n
t
i
n
u
o
u
s
6000m
Altitude
s
h
o
r
t
-
t
e
r
m
(
4
s
)
A
C
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
B
Nov. 2012 / Rev. 2.0 DS-QT40.241-EN
All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/27