Data Sheet

Modules EN54 series
Power supply modules for built-in
systems and smoke and heat control systems
M v.1.0/II
.
fire alarm
CODE
TYPE:
:
EN
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail: sales@pulsar.pl
EN54M series power supplies module
Power supplies for fire alarm systems 27,6 V DC
Pulsar
®
“This product is suitable for the systems designed
in compliance with the standards EN 54-4 and EN 12101-10”
Functional requirements
Requirements
according to
standards
Power supplies
EN54M series
Two independent power sources YES YES
External Power Supply failure indication YES YES
Two independent power supply outputs protected against short-circuit YES YES
Temperature-compensated battery charging YES YES
Measurement of the resistance of the battery circuit YES YES
Low battery indication YES YES
Recharging the battery to 80% of the rated capacity within 24 hours YES YES
Deep discharge battery protection YES YES
Short-circuit protection of battery terminals YES YES
Charging circuit failure indication YES YES
Short-circuit protection YES YES
Overload protection YES YES
Output of collective failure ALARM YES YES
EPS technical output YES YES
Low output voltage indication - YES
High output voltage indication - YES
Indication of power supply failure - YES
Overvoltage protection - YES
Input of an external failure indication EXTi - YES
RED POWER plus