Use and Care Manual

OPERA
TION
16
Do not connect 3-phase loads to generator.
CAUTION!
Extension Cord Selection
Refer to the below table to ensure the extension cord used has
the capacity to carry the required load. If the size of the
cable is inadequate it can cause a voltage drop, which can dam
age the electrical device and cord.
Current
(Amps)
Load (W
atts)
Maximum Cord Length
230V #8 Wire #10 Wire #12 Wire #14 Wire #16 Wire
2.5 600 X 1000 ft. 600 ft. 375 ft. 250 ft.
5 1200 X 500 ft. 300 ft. 200 ft. 125 ft.
7.5 1800 X 350 ft. 200 ft. 125 ft. 100 ft.
10 2400 X 250 ft. 150 ft. 100 ft. 50 ft.
15 3800 X 150 ft. 100 ft. 65 ft. X
20 4800 175 ft. 125 ft. 75 ft. X X
25 6000 150 ft. 100 ft. X X X
30 7200 125 ft. 65 ft. X X X
Moving the Generator
Disconnect any electronic devices from generator then turn generator off.
Turn fuel valve to the “OFF” position.
Tilt generator until it balances on wheels. Roll machine to desired location.
If the generator must be carried, fold handle to the down position. Never lift or carry generator by its handle.
CAUTION!
This
product
is
heavy and requires several people to lift. Lift and lower with your legs by bending
at the knees, not your back, to avoid injury.
Don’t Overload Generator
Make sure you can supply enough rated watts and surge watts for all electronic devices connected to the generator. Rated
watts refer to the power a generator must supply to keep a device running. Surge watts refer to the power a generator
must supply to start an electronic device. This power surge for starting a device usually lasts between 2-3 seconds but this
additional output must be taken into account when selecting the electronic devices you plan to attach to the generator. To
prevent overloading the generator take the following steps:
120 / 240 Volt AC, 30 Amp locking receptacle
This receptacle has a 30 Amp push-to reset circuit breaker to protect against overload.
This receptacle is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 3600 watts (3.6 kW) at 30
Amps. It is also rated to operate 240 Volt AC, single phase, 60Hz loads requiring up to 7,200 watts (7.2 kW).
Use a NEMA L14-30 plug with this receptacle.
Use a 4-wire cord rated for 240 Volts AC, 30 Amps to the plug. You can use the same 4-wire cord to operate a 120
Volt load.
12 Volt 8.3 Amp Output is for charging batteries only!
WARNING!