Instructions / Assembly

17
OPERATION
Bathroom Rated Watts Surge Watts
Hair Dryer 1250 0
Curling Iron 1500 0
Family Room
X-Box or Play Station 40 0
AM/FM Radio 100 100
VCR 100 100
Color TV (27”) 500 500
Fax Machine 65 0
Personal Computer (17” Monitor) 800 0
Laser Printer 950 0
Copy Machine 1600 0
Power Tools
1000W Quartz Halogen Work Light 1000 0
Airless Sprayer ( HP) 600 1200
Reciprocity Saw 960 0
Circular Saw (7 ¼”) 1400 2300
Mitar Saw (10”) 1800 1800
Table/Radial Arm Saw 2000 2000
Electric Drill (½ HP, 5.4 Amps) 600 900
Essentials Rated Watts Surge Watts
75W Light Bulbs 75 each 75 each
18 CU Ft Refrigerator / Freezer 800 2200
Furnace Fan ( HP) 800 2350
Sump Pump ( HP) 1000 2000
Water Pump ( HP) 1000 3000
Heating/Cooling
650 800
Table Fan 800 2000
Electric Blanket 400 400
Space Heater 1800 1800
Kitchen
Blender 300 900
Toaster (2 slice) 1000 1600
Coffee Maker 1500 1500
Electric Range (1 element) 1500 1500
Dishwasher 1500 3000
Laundry Room
Iron 1200 1200
Washing Machine 1150 3400
Gas Clothes Dryer 700 2500
Wattage Reference Guide
(Wattages listed are just approximations. Check electronic device for actual wattage)
Don’t Overload Generator
Make sure you can supply enough rated watts for all electronic devices connected to the generator. Rated watts refer to
the power a generator must supply to keep a device running. Surge watts refer to the power a generator must supply to
start an electronic device. This power surge for starting a device usually lasts between 2-3 seconds but this additional
output must be taken into account when selecting the electronic devices you plan to attach to the generator. To prevent
overloading the generator take the following steps:
1. Add up the total rated wattage of all electronic devices that will be connected to the generator simultaneously.
2. Estimate surge watts by adding the item(s) with the highest output (it is unnecessary to calculate the surge output for all
devices as they should be connected one at a time).
3. Add the Surge Watts to the total Rated Watts in step 1. Keep total load within generator’s power capacity.