Troubleshooting guide

Power VT
®
Plus WATER HEATER
14
PV500-44 12/13
6.3 Inlet Pressure
Measure at the inlet pressure tap located at the main gas cock. The inlet pressure must remain within the minimum
and maximum values while the unit is at rest and while the unit is operating at maximum firing rate.
6.4 Manifold Pressure
Measure at the pressure tap located downstream side of the manual valve closest to the burner. The rated manifold
pressure appears on the product data label located near the front of the appliance.
6.5 Gas Piping Size
Use the values in “Convert Fittings to Equivalent Straight Pipe” to add the equivalent straight pipe for each elbow or
tee to obtain the total distance from the meter.
*Multiplier for Propane: 1.57
**Multiplier for alternate pressure drops: 0.3" W.C. 0.77; 1.0" W.C. 1.41; 2.0" W.C. 2.00; and 4.0" W.C. 2.82.
INLET PRESSURE NAT. GAS LP
Maximum Static Pressure (Inches-Water Column) 14" 14"
Minimum Flow Pressure (Inches-Water Column) 4.5" 11"
CONVERT FITTINGS TO EQUIVALENT STRAIGHT PIPE
Diameter Fitting (inches) ¾" 1" 1¼" 1½" 2" 3" 4" 5"
Equivalent Length of Straight Pipe (feet) 2' 2' 3' 4' 5' 10' 14' 20'
Equivalent Feet
From Meter
SINGLE UNIT INSTALLATION SUGGESTED PIPE SIZE
Maximum Capacity for Natural Gas*
MBTU/HR Based on 0.5" W.C. Pressure Drop**
1-1/4" 1-1/2" 2" 2½" 3" 4"
25 860 1320 2475 3900 7000 -
40 660 990 1900 3000 5300 -
60 - 810 1520 2400 4300 -
80 - 690 1300 2050 3700 -
100 - 620 1150 1850 3250 6700
125 - - 1020 1650 2950 6000
150 - - 950 1500 2650 5500
175 - - 850 1370 2450 5000
200 - - 800 1280 2280 4600