Troubleshooting guide

Power VT
®
Plus WATER HEATER
17
PV500-44 12/13
Duct Fitting Equivalent Length
Duct Pipe: 6” Duct 7” Duct 8” Duct 9” Duct
90º Elbow 8 feet 9 feet 10 feet 11 feet
90º Long Radius Elbow 5 feet 5 feet 5 feet 6 feet
45º Elbow 5 feet 5 feet 5 feet 5 feet
The following remote air duct information is provided for use in design calculations, if needed.
Remote Air Duct Specifications
Input MBtu Required Air (SCFM)
399 87
500 108
750 163
900 195
1000 217
7.3 Remote Combustion Air Cap
A UL Listed air intake vent termination cap MUST be attached to the remote combustion air vent termination to
adequately protect the combustion air inlet from wind and weather. A UL Listed air intake termination cap is available
from PVI Industries and may have shipped with the water heater as a purchased option.
7.4 Vertical or Horizontal Remote Air Duct Termination
Air inlet and exhaust vents should terminate in the same wind pressure area whenever possible.
Air inlet must be located no less than 3 feet (0.91m) below the exhaust terminal if they are within 10 feet (3.05 m)
of each other.
If terminating through the roof, the air inlet must terminate at least 12 inches (0.3 m) above roof level and at least
12 inches (0.3 m) above snow levels.
If terminating through a sidewall, the air inlet must terminate at least 12 inches (0.3 m) above grade and/or at
least 12 inches (0.3 m) above normal snow levels.
Vertical Remote Air Horizontal Remote Air
7.5 Remote Air Consideration for Combined Remote Air Ducting
Each water heater MUST have separate intake piping. Consult factory for common air intake pipe sizing.