Partition Configuration Tasks
164 SL500 User’s Guide July 2008 Revision: KA 96116
Verify Partition Configurations
Use this procedure to verify partition configuration changes you have made during this
SL Console login session. This procedure warns you of the following possible errors:
A partition has orphaned cartridges. See “Orphaned Cartridges in Partitioned
Libraries” on page 152 for details.
Library resources have been removed from a partition.
A host connected to the library does not have a partition assigned to LUN 0.
Note – This procedure verifies only one partition at a time. If you need to verify
multiple partitions, you must repeat this procedure separately for each partition.
1. Select Tools > Partitions.
2. Click the Design (Step 3) tab.
The Design (Step 3) screen appears, displaying the current configuration of the library.
3. In the Partition pull-down menu, select the partition you want to verify.
All screen fields are updated to reflect the current configuration for the selected
partition.
4. In the Options Bar, click Verify.
The boundaries of the selected partition are verified, including the locations of all tape
cartridges.
Note – This verification is performed on the current partition configuration in the
SL Console partition workspace only. It does not verify current partition boundaries
against the library controller database; therefore it cannot identify configuration
conflicts that may arise due to other users performing cartridge movements or library
configuration changes—through the command line interface, other SL Console sessions,
or host applications—at the same time you have made partition changes.
The Verify Results popup appears, indicating whether there are any orphaned
cartridges or other errors in the current partition configuration.