User`s guide

INSTALLATION
Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
32
Plug-Receptacle UPS Installation
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
To install a plug-receptacle UPS:
1. If you are installing power management software, connect your
computer to the USB port, UPS communication port, or optional
X-Slot card (see page 47). For the communication port, use only the
serial cable supplied in the accessory kit.
2. If your rack has conductors for grounding or bonding of ungrounded
metal parts, connect the ground cable (not included) to the ground
bonding screw.
Load Segment
Circuit Breakers
USB Port
X-Slot
Communication
Bay
Battery Connector
REPO Port
L6-20
Receptacles
IEC 320-C13 Receptacles
Power Cord with L6-30 Plug
L6-30 Receptacle
Ground
Bonding Screw
Communication
Port
Battery Circuit Breaker
Figure 15. PW5125 5000 UPS Rear Panel
Load Segment
Circuit Breakers
USB Port
X-Slot
Communication
Bay
Battery Connector
REPO Port
IEC 320-C13
Receptacles
IEC 320-C19 Receptacles
Power Cord with 32A, IEC-309 Plug
IEC 309-32A Receptacle
Ground
Bonding Screw
Communication
Port
Battery Circuit Breaker
Figure 16. PW5125 6000i UPS Rear Panel