Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
36
Figure 18. UPS Terminal Block
Table 1. UPS Wiring Specifications
Wire
Function
Terminal
Position
UPS Wire Function
Terminal Wire
Size Rating*
Tightening
Torque
Input
4 Input Neutral
2.5–16 mm
2
(14–6 AWG)
1.8 Nm (16 lb in)
3 Input Line
Output
2 Output Neutral
2.5–16 mm
2
(14–6 AWG)
1.8 Nm (16 lb in)
1 Output Line
* Use 2.0 mm
2
(10 AWG) 75_C copper wire minimum.
8. Replace the terminal block cover.
9. If your rack has conductors for grounding or bonding of ungrounded
metal parts, connect the ground cable (not included) to the ground
bonding screw.
10. Plug the equipment to be protected into the appropriate UPS output
receptacles (see page 51 for more information on load segments).
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an
overload alarm.
11. Verify that all load segment circuit breakers are in the ON position.
12. Remove the breaker tie from all battery circuit breakers.