Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
62
Table 5. Electrical Input and Output
Nominal Voltage PW5125 5000 and PW5125 6000 HW: 200/208, 220, 230, 240V selectable
PW5125 6000i: 220, 230, 240V selectable
Voltage Range 160–288V nominal
Nominal Frequency 50/60 Hz auto-sensing
Frequency Range 50 Hz: 46–54 Hz ±4%
60 Hz: 56–64 Hz ±4%
Noise Filtering MOVs and line filter for normal and common mode noise
Input Power Factor >0.95
Regulation
(Normal Mode)
-10% to +6% of nominal voltage
Regulation
(Battery Mode)
Nominal output voltage ±5%
Voltage Waveform Normal mode: Sine wave; <5% THD with typical PFC load
Battery mode: Sine wave; <7% THD with typical PFC load and no more
than 15% at the end of battery discharge
Table 6. Weights and Dimensions
UPS Extended Battery Module (EBM)
Dimensions
(WxDxH)
44.2 x 66 x 13 cm
17.4 x 26 x 5.1 (3U)
44.2 x 68.3 x 13 cm
17.4 x 26.9 x 5.1 (3U)
Weights 73 kg (161 lb) 69.9 kg (154 lb)