Troubleshooting Guide

1.1 Indoor Unit Error Display
Operation
lamp
Timer lamp Display LED STATUS
1 time
X E0 Indoor unit EEPROM parameter error
2 times
X E1 Indoor / outdoor units communication error
3 times
X E2 Zero-crossing signal detection error
4 times
X E3 Indoor fan speed has been out of control
5 times
X E4
Indoor room temperature sensor T1 open circuit or
short circuit
6 times
X E5
Evaporator coil temperature sensor T2 open circuit or
short circuit
7 times
X EC Refrigerant leakage detection
1 times
O
F0
Overload current protection
2 times
O F1
Outdoor ambient temperature sensor T4 open circuit or
short circuit
3 times
O F2
Condenser coil temperature sensor T3 open circuit or
short circuit
4 times
O F3
Compressor discharge temperature sensor TP open
circuit or short circuit
5 times
O F4 Outdoor unit EEPROM parameter error
6 times
O F5 Outdoor fan speed has been out of control
1 times
P0 IPM malfunction or IGBT over-strong current protection
2 times
P1 Over voltage or over low voltage protection
3 times
P2
High temperature protection of IPM module or
compressor top
4 times
P3* Outdoor ambient temperature too low.
5 times
P4 Inverter compressor drive error
6 times
P5 Indoor units mode conflict (multi-zone ONLY)
7 times
P6
Low pressure protection(Only for 36K)
Olight Xoff ☆(flash
*P3
1) In heating mode, when the outdoor temperature is lower than -25 for 1 hour, the indoor unit
display error code P3.
2) If the outdoor temperature is higher than -22 for 10 minutes and compressor stop for 1 hour or
outdoor temperature is higher than -5 for 10 minutes, then the unit will return to work.
* Fault Symptom: The display board shows a garbled code or a code that is not an error code found
in the service manual nor a temperature reading.
Trouble shooting:
Use the remote controller. If the unit does not respond to the remote, the indoor PCB needs to be
replaced; if the unit does respond, then the display board needs to be replaced