Instructions / Assembly

Table 5.1
Table 5.2
Page 8
Specications
5
Outdoor Unit
Specications
Indoor units that can be used in
combination
Number of connected
units
1-5 units
Compressor stop/start frequency Stop time 3 minutes or more
Voltage uctuation within ± 10% of rated voltage
Power source voltage
Voltage drop during start within ± 15% of rated voltage
Interval unbalance within ± 3% of rated voltage
1 drive 2 1 drive 3
Max. length for all rooms 98.4/30 147.6/45
Max. length for one indoor unit 65.6/20 82/25
Max. height dierent between
indoor and outdoor unit
OU higher than IU
32.8/10 32.8/10
OU lower than IU 49/15 49/15
Max. height dierence between indoor units
32.8/10 32.8/10
1 drive 4 1 drive 5
196.8/60 246/75
98.4/30 98.4/30
32.8/10 32.8/10
49/15 49/15
32.8/10 32.8/10
Unit: ft/m
49ft (15m)
When installing multiple indoor units to a single outdoor unit, ensure that the length of the refrigerant
pipe and the drop height between the indoor and outdoor units meet the following requirements:
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
49ft (15m)
32.8ft (10m)
Max. height dierence