user manual

22
30049 40049 bit Boiler #6 Status Word Boiler #6
R 10289 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10290 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10291 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10292 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10293 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10294 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10295 6 High Limit (0 = Normal, 1 = Alarm)
R 10296 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10297 8 Manual Override (0 = Normal, 1 = Alarm)
R 10298 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10299 10 No Pilot (0 = Normal, 1 = Alarm)
30050 40050 bit Boiler #7 Status Ward
Boiler #7
R 10305 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10306 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10307 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10308 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10309 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10310 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10311 6 High Limit (0 = Normal, 1 = Alarm)
R 10312 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10313 8 Manual Override (0 = Normal, 1 = Alarm)
R 10314 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10315 10 No Pilot (0 = Normal, 1 = Alarm)
30035 40051 bit Boiler #3 Status Ward Boiler #8
R 10321 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10322 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10323 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10324 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10325 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10326 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10327 6 High Limit (0 = Normal, 1 = Alarm)
R 10328 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10329 8 Manual Override (0 = Normal, 1 = Alarm)
R 10330 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10331 10 No Pilot (0 = Normal, 1 = Alarm)
R 30052 40052 Setpoint Day Setpoint (Desired water temp @70F)
R 30053 40053 Nitesetback Night Setback (Desired water temp @ 70F)
R 30054 40054 Ratio Out 1-200 = 0.1 - 20.0 in 0.1 increments
R 30055 40055 Throttling Delta T of all boilers in system (Normally 20 / # boilers)
R 30056 40056 Modulating Step (%) min 5% steps
R 30057 40057 Wait State Time (Sec)
R 30058 40058 Outdoor Cut off Temperature (O/C)
R 30059 40059 Control Band (degrees F Tolerance from TAR) (C/B)
R 30060 40060 Lead Boiler Number (1 to Number of Boilers)
R 30061 40061 Number of Boilers
R 30062 40062 TP - Boiler Pump Delays (Min) Boiler #1
R 30063 40063 TP - Boiler Pump Delays (Min) Boiler #2
R 30064 40064 TP - Boiler Pump Delays (Min) Boiler #3
R 30065 40065 TP - Boiler Pump Delays (Min) Boiler #4
R 30066 40066 TP - Boiler Pump Delays (Min) Boiler #5
R 30067 40067 TP - Boiler Pump Delays (Min) Boiler #6
R 30068 40068 TP - Boiler Pump Delays (Min) Boiler #7
R 30069 40069 TP - Boiler Pump Delays (Min) Boiler #8
A-4