Installation manual

Regency Plateau™ PTO30 Outdoor Gas Fireplace
13
INSTALLATION
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual approved
manual shut-off valve during any pressure testing
of the gas supply piping system at test pressures
equal to or less than 1/2 psig. (3.45 kPa). Discon-
nect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits speci ed on the safety label.
6) When nished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" at screwdriver.
Note: Screw should be snug, but do not over
tighten.
AERATION ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue ame or
close for a more yellow ame.
Minimum Air Shutter Opening:
Fully Closed NG
1/2" LPG / ULPG
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
HIGH ELEVATION
This unit is approved for altitude 0 to 4500 ft. (CAN/
CGA 2.17-M91) or AS/NZS 5601.1
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or ex connectors use only
approved ttings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and ex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open ame for leak testing.
PTO30-NG SYSTEM DATA
Max. Supply Pressure 14" WC (3.49 kpa)
Min. Supply Pressure 5" WC (1.25 kpa)
Manifold Pressure 3.5" WC (0.87 kpa)
Manifold Pressure -Low 1.6" WC (0.40 kpa)
Ori ce Size #25 DMS
Minimum Input 37 mj.
Maximum Input 55 mj.
PTO30-LPG / ULPG SYSTEM DATA
Max. Supply Pressure 14" WC (3.49 kpa)
Min. Supply Pressure 11" WC (2.73 kpa)
Manifold Pressure 10" WC (2.49 kpa)
Manifold Pressure-Low 6.4" WC (1.59 kpa)
Ori ce Size #45 DMS
Minimum Input 40 mj.
Maximum Input 55 mj.
Note: If you have an incorrect ame pattern,
contact your Regency
®
dealer for further
instructions.
Incorrect ame pattern will have small, probably
yellow ames, not coming into proper contact
with the rear burner or ame sensor.
Burner
Flame Sensor
Pilot
Ignitor
PILOT ADJUSTMENT
Periodically check the pilot ames. Correct ame
pattern has two strong blue ames: 1 owing
around the ame sensor and 1 owing across
the burner (it does not have to be touching the
burner).
886 S.I.T. VALVE
DESCRIPTION
1) Manual high/low adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
1
3
2
4
5
6
7
Properly locate lines/hoses out of pathways
or arches where the hose may be subject to
damage.
Inspect hoses before each use and replace if
evidence of excessive abrasion.