INSTALLATION
Caution Requirements
The top, back and sides of the decorative gas appliance
are defi ned by standoffs. The metal ends of the
standoff may NOT be recessed into combustible
construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas
appliance be installed only in accordance with these instructions.
MINIMUM CLEARANCES TO COMBUSTIBLES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
PTO30 Clearance Requirements
E
F
Alcove
PTO30 BURNER MUST BE INSTALLED AT A MINI-
MUM OF 750MM ABOVE GROUND. IF INSTALLED
LOWER, IT IS REQUIRED TO INSTALL THE OP-
TIMAL DECORATIVE GLASS SURROUND AND
ENSURE MINIMUM HEIGHT IS 750MM TO TOP OF
GLASS SURROUND.
IF INSTALLED LOWER THAN 750MM WITH GLASS
SURROUND, INSTALLER MUST PROVIDE A
MEANS OF SECONDARY GUARD, NOT ATTACHED
TO, BUT SURROUNDING THE PTO30 BURNER
WITH A MINIMUM HEIGHT OF 750MM.
C
A
B
D
Clearance: Dimension Measured From:
A: Back wall
17" (432mm) Burner to back wall
B: Sidewall
17" (432mm) Burner to sidewall
C: Ceiling
45" (1143mm) Burner to Ceiling
D: Unit Base
1"(25mm) Unit Base to Combustible
E1: Alcove Width 30"
E2: Alcove Width 60"
84"(2134mm)
100" (2540mm)
Wall to Wall (Minimum)
F: Alcove Depth
60" (1524mm) Front to Back Wall (Maximum)
Notes:
0" No Hearth Required