3.2 Control panel
13-position switch Auto / Manual ! / TEST STB
- The switch may be left on either position manual ! or automatic AUTO.
- STB TEST: temporary action to test the safety thermostat.
- Press the TEST STB switch and set pump shut-off switch (2) 9 to the “Summer” position %.
2 Switch Burner / Heating pump:
This button is used to control the burner and the heating pump.
Both buttons are in “Winter” . position: heating and hot water production systems operate (if a hot water tank is included).
Both buttons are in “Summer” % position: The burner and the heating pump don't operate.
If the boiler is fitted with a control unit, both buttons must be left on the Winter . position.
3 Main ON/OFF switch
4 Location for hour run meter for the first and second stage (optional)
5 Boiler thermostat (30 to 90 °C):
A factory-set stop limits the maximum temperature to 75°C. The stop may be moved if necessary.
6 Stage one or stage two indicators:
These only go on if the relevant thermostat or control unit require heating and if the safety contact is closed.
7 Boiler thermometer
8 Location for flue gas thermometer (optional)
9 Safety thermostat with manual reset (set to 110 °C).
10 10 A Circuit-breaker: with delayed action and manual reset.
11 Location for optional features or a RC4/RC5 control unit
13 Switch for selecting the number of burner stages
14 Burner alarm indicator + Reset button