4 Technical characteristics
The boilers can operate on natural gas H/E or propane.
Conversion to propane is done following the operations described in
the chapter "Adaptation to another gas".
(1)
At nominal output (2nd stage)
(2)
Boiler temperature 80°C
(3)
Electrical output of the boiler only with no accessories
Conditions of use
- Maximum safety temperature: 110°C
- Maximum operating pressure: 6
bar
- Thermostat adjustable from 30 to 90°C
- Safety thermostat: 110°Put the insulation plate *1 under the burner
after unscrewing the self-tapping screw *2 pre-assembled to the
baseC
Boiler Gas 360 S/ 8 10 12 14
Useful efficiency
1st stage kW36455454
2nd stage kW 63 81 99 117
Power input
1st stage kW 39.4 49.1 58.8 58.8
2nd stage kW 68.9 88.4 107.8 127.2
Number of sections Part 8 10 12 14
Mass flue gas flow rate
(1) (2)
1st stage
Kg/h
140 166 199 199
2nd stage 138 177 216 255
Flue gas temperature Tf
(1) (2)
°C 135 135 135 135
CO
2
(Natural gas H)
(1)
% 7.4 7.4 7.4 7.4
Ionisation current
(1)
µA3333
Required depressurisation at the
nozzle
(1)
mbar 0.04 0.04 0.04 0.04
Minimum outlet temperature °C 30 30 30 30
Maximum outlet temperature °C 90 90 90 90
Maximum operating pressure bar 6 6 6 6
Electrical connection V/Hz 230/50 230/50 230/50 230/50
Electrical output
(3)
W25252525
Gas connection inchR1R1R1R1
Heating connection inch R 1 1/2 R1 1/2 R1 1/2 R1 1/2
Internal diameter flue gas nozzle mm 180 200 200 225
Water resistance
(1)
T = 10K
mbar
56 120 216 320
T = 15K 25 53 96 142
T = 20K 14 30 54 80
Water capacity* l l 32.6 39.8 47 54.2
Shipping weight kg 257 305 357 408