13. Typical applications
a) Standard wiring for a single code lock
Connecttheybackdiode(1N4004,includedwiththecodelock)tothedoorlockinseries.
Place the diode as close as possible to the lock. When an inductance is switched off (electro-
magnet in the lock), the energy released is routed through the diode. This prevents damage
to the code lock.
To prevent an electrostatic charge on the housing and keypad, connect the GND (-) output
to a neutral earthed wire.
The door LED turns on when the door output is connected. If desired, the LED can be con-
guredtostayswitchedoff.
Isolate all unused connections to prevent a short circuit.
Congurethelocktype(“Fail-Safe”or“Fail-Secure”)withprogramcode66.
The use of a door sensor (input T7) is optional. If no sensor is used, this input must be bridged
toGND.Whenasensorisconnected,thedoorlockcanbeconguredtodothefollowing:
- Automatically disable the lock when the door is closed.
- Trigger an alarm when the door is forced open.
- Sound a warning alarm when the door stays open for a preset duration.
12 V/DC
POWER
SUPPLY
DOOR OPENER
CABLE HARNESS
41