5. Electrical Installation
5.1 Electrical Specifications
The electrical characteristics are within ±10 percent of the indicated
values of Isc, Voc, and Pmax under Standard Test Conditions (STC
Irradiance of 100mW/cm
2
, AM 1.5 spectrum, and a cell temperature
of 25°C (77°F))
Under normal conditions, a photovoltaic module is likely to
experience more current and/or voltage than its Standard Test
Condition’s rated output. Accordingly, the values of Isc and Voc
marked on this module should be multiplied by a factor of 1.25 when
determining component voltage ratings, conductor ampacities, fuse
sizes, and size of controls connected to the PV output. (Additional
multiplier of 1.56 may be applicable when sizing conductors and
fuses)