section. Deviating from these procedures could expose you to lethal
voltage.
WARNING!
Always turn OFF all switches in the PV system before connecting any
wires to or disconnecting any wires from the Digiwatts unit.
Information
The DC input and AC output circuits are isolated from the enclosure and
system grounding, as required by section 250 of the National Electric
Code, ANSI/NFPA 70. Similarly, such isolation of DC input and AC
output circuits from enclosure and system grounding is also required by
the CANADIAN ELECTRICAL CODE, PART 1. It is the responsibility
of the installer to maintain this isolation.
The Photovoltaic System Grounding shall be installed per the
requirements of sections 690.41 through 690.47 of the National Electric
Code, ANSI/NFPA 70. It is the responsibility of the installer to meet
these requirements.
AC Grounding
The Digiwatts unit must be connected to the AC ground from the utility via the
Ground Terminal. Use 8AWG-12AWG, 105°C, copper wire for AC grounding.
PV Grounding
The PV array ground should be connected to the PV Grounding and DC
Grounding Electrode Conductor. Use 8AWG-10AWG, 105°C, copper wire for PV
grounding.