Installation guide

Installation Guide RN3000US Jan13
52
9.2 Trip Limits / Trip Times
Nominal
Freq. (Hz)
Trip Limit (Hz) Trip Freq. (Hz) Trip Times (s)
>60.5 60.45 - 60.55 max. 0.1602
60
<59.3 59.25 - 59.35 max. 0.1602
Nominal
Voltage (V)
Trip Limit
Trip Voltages
Line-to-Neutral (V)*
Trip Times(s)
50% 119 - 121 max. 0.1602
88% 210 - 212 max. 2.002
110% 261 - 263 max. 1.002
240
120% 287 - 289 max. 0.1602
NOTE:
This unit or system is provided with fixed trip limits and shall not be
aggregated above 30 kW on a single Point of Common Connection.
9.3 Torque Values and Wire Sizes
Te rminal
Install Torque
(Nm / ft-lbs)
Wire Size
AC & DC Terminal Blocks (Phoenix) --
8AWG-12AWG
Cover Machine Screws 4 / 2.9 --