Replacement Parts Guide

Form P-RG/RP/RBL, P/N 263984R2, Page 42
Assembled Replacement Downturn Plenum Cabinet - If a downturn plenum cabinet needs to be added to the system at the
installation site, order the appropriate P/N (above) for a factory-assembled cabinet. Since this cabinet is not factory-built on the
system curb cap, a platform or legs must be eld fabricated to support the downturn plenum cabinet. Do not support the downturn
plenum cabinet with the ductwork. The ductwork connection and roof opening must be ashed and/or sealed to prevent water from
entering the ductwork or the building.
Optional Downturn Plenum and Discharge Damper - Applies to Model Series RGB/RPB, Model
Series RGBL/RPBL, and Blower Cabinet Model RBL
"Attached"
Downturn
Plenum
with Door
Panel
Removed
"Unattached"
Downturn Plenum
510
511
513
514
515
517
Assembled Replacement
Downturn Plenum Cabinet less
Curb Cap (no dampers)
RGB/
RPB
Series
75-125 147140
150-175 147141
200-225 147142
250-300 147143
350 147144
400 147145
RGBL/
RPBL
Series
500, 600 147147
750, 1050 147148
400, 800, 1200 147146
Model RBL 147146
Code
Model RPBL, RGBL, PGBL Sizes
500/600 750/1050 400/800/1200
Model (C)(H)RGB/RPB Sizes
75/100/125 150/175 200/225 250/300 350 400
625 Downturn Plenum Bottom Assembly 103586 103587 103588 103589 103590 103591
626 Downturn Plenum Top Assembly 103611 103612 103613 103614 103615 103616
627
Downturn Plenum Top Assembly
Insulation Retainer
100253 100254 100255 100256 100257 100258
628
Downturn Plenum Front Panel Assy 103617 103618 103619 103620 103621 103622
Downturn Plenum Front Panel
Assembly (w/double wall, Opt AY3)
105547 105548 105549 105550 105551 105552
629
Downturn Plenum Door Assembly (2) 100349
Downturn Plenum Door Assembly (w/
double wall, Option AY3)
(2) 104114
630 Downturn Plenum Corner Post (2) 114761
631 Downturn Plenum Corner Post Cap (2) 100072
632 Downturn Plenum Cabinet Leg (2) 100027
633
Downturn Plenum Cabinet Leg Cap 100069
Downturn Plenum Cabinet Leg Cap 100070
634 Downtrun Plenum Top Insulation Clamp (4) 110537
635 Door Latch Assy - All cabinet Doors 112974
Instructions for Attaching Replacement Cabinet
1) If the heater is operating, turn off the gas and the electric.
2) Position the "open" side of the cabinet against the heater discharge.
The top and side posts of the cabinet will "overlap" the heater.
Fasten on both sides and across the top with eld-supplied, weather-
resistant sheet metal screws.
3) Provide eld-fabricated, weather-resistant support for the cabinet.
4) Attach ductwork to the ange on the cabinet. Flash and/or seal the
ductwork and the roof opening to prevent water from entering the
building or the ductwork.
5) Turn on the electric and the gas. Follow the instructions on the
lighting instruction plate. Check the heater for proper operation.
Discharge Damper and Controls
(See linkage illustrations below.)
Size (see
Models on
chart left)
P/N
636 Discharge Damper
75/100/125 15868
150/175 15869
200 - 1200 12634
637
Discharge Damper and Frame
Assembly
75/100/125 105421
150/175 105422
200 - 1200 105423
638 Discharge Damper Motor Base
All
113873
639 Discharge Damper Motor Cover 113874
640
Damper Motor, Honeywell
M6161A1001
114429
641
Auxiliary End Switch, Honeywell
201052A
114430
642 Shaft 113775
643 Damper Arm, Honeywell 26026K (2) 12635
644 Ball Joint, Honeywell 27518 (2) 12636
645 Damper Rod, 9-1/2" long 114467
RIGHT SIDE
DAMPER CLOSED
DAMPER ARM
P/N 12635
SET ARM AT O'CLOCK
9-1/2" LG. DAMPER ROD
P/N 114467
BALL JOINT
P/N 12636
SET AT END
OF ARM
DAMPER ARM - P/N 12635
SET ARM AT O'CLOCK
BALL JOINTP/N 12636
SET AT 48
AQ8 - AJ2
FRONT
DISCHARGE
DAMPER MOTOR REZNOR P/N 114429;
DAMPER MOTOR AUX. SWITCH P/N 114430
(SET SWITCH TO 70~ - DAMPER 20% OPEN)
MOTOR BASE
P/N 113873
MOTOR COVER
P/N 113874
(2) MINIMUM
POSITION
ADJUSTMENT
BOLTS
P/N 114485
LEFT SIDE
DAMPER CLOSED
DAMPER ARM
P/N 12635
SET ARM AT
10:00 O'CLOCK
9-1/2" LG. DAMPER ROD
P/N 114467
BALL JOINT
P/N 12636
SET AT END OF ARM
DAMPER ARM P/N 12635
SET ARM AT 10:00 O'CLOCK
BALL JOINT
P/N 12636
SET AT 48
AQ8 - AJ1
FRONT
DISCHARGE
DAMPER MOTOR REZNOR P/N 114429;
DAMPER MOTOR AUX. SWITCH P/N 114430
(SET SWITCH TO 70 ~ - DAMPER 20% OPEN)
MOTOR BASE
P/N 113873
MOTOR COVER
P/N 113874
(2) MINIMUM POSITION
ADJUSTMENT BOLTS
P/N 114485
Damper Linkage -
Option AQ8
AJ1 indicates left side
controls; AJ2 indicates
right side controls.
Code 650 - Roof Curbs - 16" (same as CJ Options)
Roof Curb Model Series RGBL and RPBL
Model
RBL
Model Series RGB and RPB
Description 400 500/600 700 800 1050 1200 75/100/125 150/175 200/225 250/300 350 400
Complete Curb Package - Std System 107251 107252 107253 107254 107255 107256 111944 105215 105216 105217 105218 105219 105220
Curb Side Assembly (2) 107257 107258 107258 107258 107259 107259 111940 105221 105221 105221 105221 105221 105221
Curb Front & Back Assembly (2) 104657 104655 104656 104657 104656 104657 104657 104652 104653 104654 104655 104656 104657
Complete Curb Pkg with a Downturn Plenum 107270 107271 107272 107273 107274 107275 111381 104673 104674 104675 104676 104677 104678
Curb Side Assembly (2) 107276 107277 107277 107277 107278 107278 111385 104649 104649 104649 104649 104649 104649
Curb Front & Back Assembly (2) 104657 104655 104656 104657 104656 104657 104657 104652 104653 104654 104655 104656 104657
Complete Curb Pkg with Cooling Coil
Cabinet, AU2 or AU3
174102 174103 174104 174105 174106 174107
Curb Side Assembly (2) 104649 104649 104649 104649 104649 104649
Curb Side Assembly (2) 172867 172868 172869 172870 172871 172872
Curb Front & Back Assembly (2) 104657 104655 104656 104657 104656 104657
Complete Curb Pkg with Cooling Coil
Cabinet & Downturn Plenum, AU11, AU12,
AU13, or AU14
174108 174109 174110 174111 174112 174113
Curb Side Assembly (2) 104649 104649 104649 104649 173606 173606
Curb Side Assembly (2) 172879 172880 172881 172882 172883 172884
Curb Front & Back Assembly (2) 104657 104655 104656 104657 104656 104657
Model RPDBL 800 1000 &1200 1400 1600
Roof Curb Pkg w/Downturn 177171 177177 177179 177181
Roof Curb Pkg w/o Downturn 177172 177178 177180 177182
Curb Hardware and Tape
P/N Description
16247 Hex Head Cap Screw 5/16" x 3/4" long
1035 Hex Nut 5/16"-18
16243 Lag Screw 5/16" x 1" long
1333 Lockwasher 5/16"
66302 50 ft, 1/4" x 1-1/4" Foam Sealant Tape