Replacement Valves

Form P-VALVES, P/N 263995, Page 19
1
G/C = General Controls; J/C = Johnson Controls; M/H = Minneapolis Honeywell;
M/N = McQuay- Norris; R = Robertshaw; W/R = White-Rodgers
2
Functional replacement may require eld-furnished reducers and/or nipples.
Replacement valves subject to change without notice.
3
This item is no longer available. Suggest you contact the control manufacturer for
replacement or functional replacement.
4
Original no longer available. Contact Reznor
®
representative to determine availabil-
ity of functional replacement. Provide complete Model No., type of gas, and type of
pilot.
5
Single-stage solenoid valve.
6
Two-stage solenoid valve.
7
Combination valve consisting of automatic gas valve, pilot line lter, pressure regu-
lator, pilot shutoff, manual shutoff, and safety pilot, all in one body.
8
Combination valve consisting of automatic gas valve, manual shutoff, pilot shutoff,
and safety pilot, all in one body.
9
Same as
8
except 115 volts and less manual shutoff.
10
J/C #H91LG-8, 3/4", may require eld supplied 3/4 x 1/2 bushings.
11
When used as a functional replacement, this valve replaces valve and pressure
regulator on unit and safety pilot.
12
Requires male compression nut, P/N 9664 (Baso #43283-2), for 1/4" pilot tubing
connection (remove pilot tubing tting supplied with valve). Some replacement
applications require eld-supplied 3/4x1/2 bushing and/or pipe nipple. If installed
on Model (C)XL(B), (C)EEXL(B), or EEDU, a new bracket for assembling the valve
and ignition controller is required; order P/N 124019.
13
Single-stage solenoid valve, 115 volt
14
Combination two-stage valve consisting of solenoid and regulator, all in one body.
15
Same as Note
14
, except 115 volt
16
Combination side entrance valve consisting of automatic gas valve, pilot line lter,
pressure regulator, pilot shutoff, manual shutoff, safety pilot, all in one body.
17
Same as Note
16
except less regulator.
18
Combination valve consisting of automatic gas valve and manual shutoff, all in one
body.
19
Combination valve consisting of automatic gas valve, pilot line lter, pressure regu-
lator, pilot shutoff, and manual shutoff, all in one body, less safety pilot.
20
For replacement of ECO adapter only on original valve, see page 26. The ECO
adapter on the replacement valve is not eld replaceable.
21
Combination valve consisting of automatic gas valve, pilot solenoid, pilot line lter,
pressure regulator, pilot shutoff, manual shutoff, all in one body, less safety pilot.
22
Combination two-stage valve consisting of solenoid, regulator, pilot line lter, and
manual shutoff, all in one body.
23
Modulating redundant valve consisting of solenoid, regulator, and manual shutoff,
all in one body, less safety pilot.
24
Pilot line solenoid valve on original unit must be removed.
25
If installed on a Model (C)XL(B), (C)EEXL(B), or EEDU, a new bracket for assem-
bling the valve and ignition controller is required; order P/N 124019.
26
Combination valve consisting of automatic gas valve, regulator, safety pilot or igni-
tion controller, all in one body.
27
Combination two-stage valve consisting of solenoid, regulator, pilot shutoff, manual
shutoff, and safety pilot, all in one body.
28
Special 1/2" H91EG drilled #42 used as low stage on XL30; also used as standard
1/2" H91EG as high stage.
29
Combination valve consisting of automatic gas valve, regulator, safety pilot or igni-
tion controller with lockout, all in one body.
30
Combination two-stage valve consisting of solenoid, regulator, pilot valve, manual
shutoff, all in one body.
NOTES for pages 11-
18, "Type of Valve
Originally Supplied"
(continued)