Clearance from Combustibles/Installation
Models RIH/RIHV - High Intensity Infrared Heaters
INSTRUCTIONS:
1. Hang full length chains at desired
height and attach to back of heater
(C) with S-hooks.
2. Attach one end of the 11” (279mm)
length chain with S-hooks to front
of heater (D).
3. Place other end of chain with S-
hooks in loop (B) on the full length
chain.
4. Check degree of angle mounting.
Adjust degree of mounting angle
by moving “S” hooks at point B.
5. Check to be sure unit is level. Crimp
all “S” hooks closed.
®
A
Model RIHN 30 is not available in Canada.
B
Model RIHN60 in Canada requires addition of wire grid, Option DN2.
C
See allowable mounting angles on previous page.
B
C
D
S
A
#5 S Hook (Typ)
11 inches/279 mm
Length Chain
with S-Hooks
Degree of
Angle
Mounting
Adjust Length to
Change Mounting
Angle
Below
Clearance
Back
Clearance
Top
Clearance
Optional
Parabolic
Reflector
Clearance from Combustibles (See diagram below)
Natural Gas Models Propane Gas Models
RIHN 30
A
RIHN 60
B
RIHVN 100
C
RIHVN 150 RIHVN 160
C
RIHVN 200 RIHL 50
C
RIHVL 90
C
RIHVL 120
C
inches
30 30 36 46 48 48 30 36 46
mm
762 762 914 1,168 1,219 1,219 762 914 1,168
inches
30 30 30 33 33 33 30 30 33
mm
762 762 762 838 838 838 762 762 838
Top Clearance
inches
60 60 62 64 68 68 60 62 64
mm
1,524 1,524 1,575 1,626 1,727 1,727 1,524 1,575 1,635
inches
48 48 50 58 68 68 48 50 58
mm
1,219 1,219 1,270 1,473 1,727 1,727 1,219 1,270 1,473
inches
34 34 38 28 38
mm
864 864 965 711 965
Below Clearance
inches
80 80 105 125 140 140 80 105 125
mm
2,032 2,032 2,667 3,175 3,556 3,556 2,032 2,667 3,175
inches
110 110 135 165 180 180 110 135 165
mm
2,794 2,794 3,429 4,191 4,572 4,572 2,794 3,429 4,191
N/A N/A N/A N/A
Side Clearance
Back Clearance
Standard Reflector
With Parabolic
Reflector, Option
DM2 or DN4
Mounted 0-29° (no
heat deflector)
Mounted 30° only
(no heat deflector)
Mounted 0-30° with
Heat Deflector,
Option DO2 or DN4
COVERAGE -
For complete space heating coverage, maximum distance between
heaters is two times the mounting height.
Recommended Distances for Units Mounted HORIZONTALLY
Distance from the Wall
Model
With Standard
Reflector
With Parabolic Reflector,
Option DM2 or DN4
RIHN 30
8 ft (2.4M) 5 ft (1.5M) 90 ft (27.4M)
RIHL 50 & RIHN 60
12 ft (3.7M) 9 ft (2.7M) 100 ft (30.5M)
RIHVL 90 & RIVN 100
16 ft (4.9M) 12 ft (3.7M) 110 ft (33.5M)
RIHVL 120
18 ft (5.5M) 14 ft (4.3M) 115 ft (35.1M)
RIHVN 150
20 ft (6.1M) 15 ft (4.6M) 12 ft (36.6M)
RIHVN 160 & RIHVN 200
24 ft (7.3M) 20 ft (6.1M) 130 ft (39.6M)
Maximum
Distance
Between
Heater Rows