Submittal

Page 15
Page __________ of __________
Location/Installation
Models RIH/RIHV - High Intensity Infrared Heaters
®
MODEL
ALLOWABLE MOUNTING
ANGLE RANGE IMPORTANT
RIHN 30 HORIZONTAL to 30 deg.
RIHL 50 HORIZONTAL to 30 deg.
RIHN 60 HORIZONTAL to 30 deg.
RIHVL 90 5 to 29 deg.
RIHVN 100 5 to 29 deg.
RIHVL 120 HORIZONTAL to 30 deg.
RIHVN 150 HORIZONTAL to 30 deg.
RIHVN 160 5 to 29 deg.
RIHVN 200 HORIZONTAL to 30 deg.
MOUNTING ANGLE MUST BE WITHIN THE TOLERANCE ALLOWED
When angle mounted, all RIHV Models must
be installed with the gas manifold on the lower
end.
When angle mounted, RIH Models must be
installed with the gas valve on the high side.
Do not angle heaters more than 30º.
MINIMUM MOUNTING HEIGHT
With Standard Reflector With Parabolic Reflector, Option DM2 or DN4
HORIZONTAL 30° HORIZONTAL 30°
Model ft M ft M ft M ft M
RIHN 30
11.0 - 13.0 3.4 -4 10.0 -12.0 3 - 3.7 N/A N/A
RIHL 50*
13.5 - 15.5 4.1 - 4.7 12.5 -14.5 3.8 -4.4 15.5 - 18.5 4.7 - 5.6 14.0 -17.0 4.3 - 5.2
RIHN 60
14.5 - 16.5 4.4 -5 13.0 -15.0 4 - 4.6 16.0 - 20.0 4.9 - 6.1 15.0 -18.0 4.6 - 5.5
RIHVL 90*
16.0 - 18.5 4.9 - 5.6 14.5 -17.0 4.4 -5.2 19.5 - 22.5 5.9 - 6.9 17.5 -20.5 5.2 - 6.2
RIHVN 100*
17.0 - 19.5 5.2 - 5.9 15.0 -17.5 4.6 -5.3 20.5 - 23.5 6.2 - 7.2 18.5 -21.5 5.6 - 6.6
RIHVL 120*
17.5 - 21.0 5.3 - 6.4 15.5 - 18.5 4.7 - 5.6 21.5 - 25.0 6.6 - 7.6 20.0 - 23.0 6.1 - 7
RIHVN 150
18.5 - 22.5 5.6 - 6.9 16.5 -20.0 5.0 -6.1 24.0 - 27.5 7.3 - 8.4 21.5 -24.5 6.6 - 7.5
RIHVN 160*
19.0 - 23.0 5.8 - 7.0 17.0 -20.5 5.2 -6.2 25.0 - 28.5 7.6 - 8.7 22.5 -25.5 6.9 - 7.8
RIHVN 200
20.5 - 25.0 6.2 - 7.6 18.5 -22.5 5.6 -6.9 27.0 - 31.0 8.2 - 9.4 24.5 -28.0 7.5 - 8.5