TECHNICAL DATA
Model UEAS
C
Output capacities shown are for units installed at elevations up to 2,000 ft. (600M).
D
Sizes shown are for gas connection to a single-stage gas valve, not gas supply line size.
E
MOP = 2.25 x largest motor FLA + remaining load. Answer is rounded down to the next size of commercially available circuit breaker or fuse.
F
All other information in this table is based on a heater equipped with standard 115 Volt open fan motor.
MODEL NUMBER 130 180 260 310
INPUT HEATING CAPACTITY
BTUH 131,000 175,000 260,000 305,000
KW/H 38.4 51.2 76.1 89.3
THERMAL EFFICIENCY 93% 91% 92% 91%
OUTPUT HEATING CAPACITY
C
BTUH 121,830 159,250 239,200 277,550
KW/H 35.7 46.6 70.0 81.3
GASCONNECTION(INCHES)
D
NATURAL 1/2 1/2 3/4 3/4
PROPANE 1/2 1/2 3/4 3/4
VENTCONNECTIONDIAMETER(INCHES) 4 4 4 4
COMBUSTIONAIRINLETDIAMETER(INCHES) 6 6 6 6
CONTROLAMPS(24-VOLT) 1.0 1.0 1.0 1.0
FULL-LOADAMPS(115V) 6.3 6.3 10 10
MAXIMUMOVERCURRENTPROTECTION(115V)
E
15 15 20 20
NORMALPOWERCONSUMPTION(WATTS) 657 657 1020 1020
DISCHARGEAIRTEMPERATURERISE(°F) 50 60 50 60
AIR VOLUME
CFM 2256 2458 4430 4283
M
3
/MINUTE 63.9 69.6 125.4 121.3
DISCHARGE AIR OPENING AREA (FT.
2
) 2.56 2.56 4.79 4.79
OUTLETVELOCITY(FPM)
FPM 883 962 924 894
M/MINUTE 269 293 282 272
FAN MOTOR HP
F
STANDARD 1/4 1/4 1/2 1/2
OPTIONAL ENCLOSED 1/4 1/4 1/2 1/2
FAN MOTOR RPM 1050 1050 1050 1050
FANDIAMETER(IN.) 18 18 24 24
APPROXIMATE CONDENSATE PER
HOUR
Gallons 1 1 2 2
Liters 3.8 3.8 7.6 7.6
APPROXIMATE NET WEIGHT
LBS 230 245 360 395
KG 104 111 163 179
APPROXIMATE SHIP WEIGHT
LBS 255 270 385 420
KG 116 122 175 190
HOW IT WORKS
Following is a diagram showing the air ow
patterns for Model UEAS. Thin arrows show
air ow from combustion air intake, across the
burner, through primary and secondary heat
exchangers and out exhaust vent. Larger ar-
rows show air ow across the heat exchanger
to provide heat to the space.
Horizontal or vertical combustion air/vent kit including concentric adapter
B
Thermostat
Thermostat guard with locking cover
Vertical louvers
Downturn nozzle kits
Manual shutoff valves
B
Selection of either a horizontal or vertical combustion air/vent kit is required.