“Cover” is given in square feet (square meters). Example 484 square feet equals an area measuring
22 feet by 22 feet.
EFFECTIVE HEAT COVER AND AIR THROW
Size Fan Motor
Horizontal Discharge Vertical Discharge
Max Mounting
Height
Throw
Max Mounting
Height
Cover H H
ft m ft m ft m ft
2
m
2
18/24
Low Speed 10 3 16 5 10 3 344 32
High Speed 10 3 23 7 11 3.5 473 44
23/33
Low Speed 10 3 16 5 10 3 366 34
High Speed 10 3 25 7.5 11 3.5 516 48
44/62
Low Speed 10 3 18 5.5 11 3.5 387 36
High Speed 11 3.5 26 8 13 4 538 50
60/85
Low Speed 11 3.5 25 7.5 13 4 484 45
High Speed 13 4 36 11 15 4.5 646 60
78/110
Low Speed 11 3.5 33 10 15 4.5 538 50
High Speed 13 4 46 14 16 5 753 70
96/120
Low Speed 13 4 33 10 15 4.5 538 50
High Speed 15 4.5 46 14 16 5 753 70
140/175
Low Speed 15 4.5 39 12 16 5 646 60
High Speed 16 5 52 16 18 5.5 861 80
190/238
Low Speed 16 5 46 14 18 5.5 968 90
High Speed 18 5.5 59 18 20 6 1184 110
300/350
Low Speed 18 5.5 66 20 23 7 1399 130
High Speed 20 6 85 26 30 9 1722 160