owner's guide water heater 260 Litre

INSTALLATION
16
OUTDOOR INSTALLATION
The water heater is to be installed at
ground level on a concrete or brick
plinth (fire proof base) and must stand
vertically upright with the back of the
water heater against an external wall
or alternatively against a fireproof
screen extending at least 500mm
above, below and either side of the flue
terminal. Failure to observe this
precaution can cause problems in high
wind areas. A secondary flue is not
required.
As a guide the following requirements extracted from the Australian Gas
Installations Standard AS 5601, must be observed:
At least 300mm between the top of
the water heater and the eaves.
At least 500mm between the water
heater and the edge of any opening
into the building, measured
horizontally and vertically.
At least 500mm between the water
heater and a return wall or external
corner, measured horizontally along
the wall.
At least 500 mm below any
openable window.
At least 500mm clear of any combustibles.