Specification Sheet

Air
Electrical and Physical Data
RASL- JEC Series
39
Model
Number
16AJL
ELECTRICAL PHYSICAL
Phase
Frequency (Hz)
Voltage (Volts)
Compressor
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil
Refrig.
Per
Circuit
Oz. [g]
Weight
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
Rev. 5/8/2012
025JEC 1-60-208/230 11.7/11.7 58.3 2.8 18/18 25/25 25/25 15.8 [1.47] 1 2500 [1180] 138 [3912] 206 [93.4] 219 [93.4]
037JEC 1-60-208/230 15.3/15.3 83 2.8 22/22 30/30 35/35 23.01 [2.14] 1 3400 [1604] 186 [5273] 216 [98] 229 [98]
039JEC 1-60-208/230 17.9/17.9 96 2.8 26/26 30/30 40/40 23 [2.14] 2 3500 [1652] 268 [7598] 326 [147.9] 345 [147.9]
048JEC 1-60-208/230 26.9/26.9 117 2.8 37/37 45/45 60/60 23 [2.14] 2 3500 [1652] 253 [7173] 326 [147.9] 348 [147.9]
060JEC 1-60-208/230 28.2/28.2 146 2.8 39/39 50/50 60/60 23 [2.14] 2 3500 [1652] 241 [6832] 328 [148.8] 346 [148.8]
NOTE: Factory Refrigerant Charge includes refrigerant for 15 feet of standard line set.
[ ] Designates Metric Conversions
Electrical and Physical Data