Specifications

TM024 Premier Loline Solar Drain back Service Instructions REV: A
D.O.I: 12/12/2007
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
29
Fault Finding Tests 3A – 4B
Test 3A – EWT Type Thermostat Test 3B – ST Type Thermostat
Warning - Ensure power is
isolated before conducting this
test.
Using a multimeter on the ohms scale,
measure between the terminals of the
mechanical thermostat. The following
results should be obtained:
3L & 4L – 0 ohms.
Warning - Ensure power is
isolated before conducting this
test.
Using a multimeter on the ohms scale,
measure between the terminals of the
mechanical thermostat. The following
results should be obtained:
3 & 4 – 0 ohms.
Test 4A – EWT Type Thermostat Test 4B – ST Type Thermostat
Warning - Ensure power is
isolated before conducting this
test.
Using a multimeter on the ohms scale,
measure between the terminals of the
mechanical thermostat. The following
results should be obtained:
1L & 2T – 0 ohms.
Warning - Ensure power is
isolated before conducting this
test.
Using a multimeter on the ohms scale,
measure between the terminals of the
mechanical thermostat. The following
results should be obtained:
1 & 2 – 0 ohms.