Fault Finding Tests 8 – 9B
Test 8
Warning – ‘Live’ equipment wear Personal Protective Equipment when
conducting this test.
Using a multimeter on the AC voltage scale, measure between the N/O terminal of the
pump relay and neutral on the control board power supply plug.
Normal reading is 240 Volts.
Test 9A – Pump 1 Test 9B – Pump 2
Warning - Ensure power is
isolated before conducting this
test.
Using a multimeter on the ohms scale,
measure between the N/O terminal of the
pump relay and the first terminal on the
right of the pump 1 plug socket.
Normal reading is 127.8 ohms.
Warning - Ensure power is
isolated before conducting this
test.
Disconnect the pump 2 plug socket from
the control board and using a multimeter
on the ohms scale, measure between the
two terminals of the pump 2 plug socket.
Normal reading is 127.8 ohms.