Technical data

18
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
Bypass voltage
thresholds
Selects the permitted
voltage range for switching
to the bypass
Low: 180V
High: 264V
Low: 180 - 200 in 1V steps
High: 250 - 264 in 1V steps
Bypass voltage
threshold for ECO
Selects the permitted
voltage range for operation
in ECO mode
Low: 200V
High: 253V
Low: 180 - 220 in 1V steps
High: 240 - 264 in 1V steps
Intervention
sensitivity for
ECO
Selects the intervention
sensitivity during operation
in ECO mode
Normal
Low
Normal
High
Power-on delay
Waiting time for automatic
switching back on after
mains power returns
5 sec.
Disabled
(1 - 255) sec. in 1 sec steps
Remote power-
on/off function
Selects the function
associated with the RS232
connector.
Disabled
Disabled
Remote ON
Remote OFF
Remote ON/OFF