Technical data

19
COMMUNICATION PORTS
On the back of the UPS (see UPS Views), the following communication ports are present:
RS232 connector
USB connector
Expansion slot for additional communication cards
RS232 CONNECTOR
RS232 CONNECTOR
PIN # SIGNAL NOTES
1
Programmable output *:
[default: UPS in lock]
(*) Opto-isolated contact max. +30Vdc / 35mA.
These contacts can be associated with other events using
the software provided
(**) Opto-isolated command +5 - 15Vdc.
These contacts can be associated with other events using
the software provided
For further information about interfacing with the UPS, refer to
the manual provided
2 TXD
3 RXD
4
Programmable input **:
[default: disabled]
5 GND
6 Power supply DC (I
max
= 20mA)
7
Programmable input **:
[default: disabled]
8
Programmable output *:
[default: low battery pre-alarm]
9
Programmable output *:
[default: battery operation]
COMMUNICATION SLOT
The UPS is equipped with an expansion slot for optional communication
cards (see figure on right) which allows the device to communicate using
the main communication standards.
Some examples:
Second RS232 and USB port
Serial duplicator
Ethernet network card with TCP/IP, HTTP and SNMP protocols
JBUS / MODBUS protocol converter card
PROFIBUS protocol converter card
Card with relay isolated contacts
To check whether further accessories are available, consult the website: www.riello-ups.com