Venting Installation Instructions

General Installation Instructions
Joint connection
Coping with condensation
Appliance connection (male appliance top)
Appliance connection (female appliance top)
Vent connections must be firmly pressed together so that the gaskets form
an airtight seal. To complete the joint connection, secure with three #8x1/2" sheet metal
screws. Secure the vent to the wall or ceiling with pipe clamps or perforated hanger iron.
Vent lengths greater than 5ft. should pitch a minimum 1/4"/ft. (1°) to the appliance.
Note: see exception under Condensate on page 4.
For a male appliance top, the first vent component to the appliance must be a vertical
discharge adapter or a horizontal discharge adapter. Never use a vent extension as the first
component to a male appliance top.
Installations with a female appliance top do
not need an appliance adapter or a
condensate collector. Simply insert the male
end of a vent component into the female
appliance top and use the integrated
condensate collector.
6