Installation guide

16 | Rinnai Continuous Flow Water Heating Specication Guide 02-13
General ue clearances - external models
The following diagram has been provided to assist in determining where, and if an
external continuous flow water heater can be installed. If in doubt, consult a licensed
gasfitter who will have access to 'Minimum clearances required for balanced flue
terminals, fan-assisted flue terminals, room-sealed appliance terminals and openings of
outdoor appliances' from AS/NZS 5601.1 (p. 94-95).
G
Dim. Infinity VT, HD200,
EF models
Infinity HD250
models
A Min. 300 mm Min. 500 mm
B Min. 300 mm Min. 500 mm
C Min. 1.5 m Min. 1.5 m
D Min. 500 mm Min. 500 mm
E Min. 300 mm Min. 300 mm
F Min. 300 mm* Min. 300 mm*
G Min. 300 mm Min. 300 mm
Clearance below eaves, balconies, and other
projections for all models is 300 mm.
* Rinnai recommend 1.5 m to give enough clearance
for the pipe work, and to safely expel flue gases.