Installation guide

44 | Rinnai Continuous Flow Water Heating Specication Guide 02-13
Rinnai Innity HD error switch
Specification summary
Code
R1070
Description
The Rinnai Infinity HD water heater
error indication switch is a volt-free,
normally open switch. The switch will
shift to a closed position when there
is an active error in the water heater.
The switch is intended to be
connected to a monitoring system
such as a building management
system, or other visual or audible
error indication system.
Suitability
Can be used with the following water
heaters:
- HD200 external
- HDi200 internal
- HD250 external
- EFi250 internal
- EF250 external
System design
System designers should note that
some errors (and hence the switch)
will reset to an inactive (open)
state under particular conditions.
It is important that this is clearly
understood when developing
monitoring and response systems.
Switch rating
The HD Error Indication Switch will
switch the following maximum loads:
- Voltage (AC or DC): 24 Volts
- Current: 1 Amp
Systems requiring loads greater than
this should be configured via an
external relay.