Complaint Description Solution
Temperature drop of the
DHW (Combi)
1. Flow reducing valve Check ow reducing valve for the correct type
in accordance with the installation instructions
2. Thermostatic mixing valve incorrectly set. Adjust (by measuring the temperature)
3. DHW power for the boiler is set too low. -Check PARA chapter Step No. 43
- Check the functioning and wiring of the
DHW sensor T3.
temperature drop of the
Solo hot
water with the DHW
cylinders
1. Synchronising valve Check the setting in accordance with
the illustrated DHW cylinder installation
instructions
2. Thermostatic mixing valve incorrectly set Adjust by measuring the temperature
3. Hot water temperature too low Check PARA chapter Step No. 31 or RS100 is
set too low. Check the functioning and wiring
of the DHW sensor T3
4. Hot water power for the boiler is set too
low.
Check PARA chapter Step No. 43
radiators do not get hot
enough or warming them
up takes too long
1. Check setting of room thermostat or
RS100
See installation and user manual RS100
2. Supply water temperature too low. Check setting PARA chapter Step No. 1 and
increase if necessary
3. Incorrect choice of installation PARA chapter Step No. 2 if necessary change.
4. Installation resistance too high (given an
average T > 36°F the boiler decreases
the load).
- See installation instructions.
- Check / clean water lter check dimensions
of pipes.
- If necessary, increase pump rpm Para 48.