Engineering Specs

5
a. ELECTRICAL: The Patio Control Panel will provide 24 Vac power to the heaters. The
installer will provide a 120V/24V/60HZ transformer with a minimum capacity of 40VA for
the first heater plus 20VA for each additional heater to be controlled by the panel.
4.03 Other Heater Ancillaries
A. Gas Connection
Each heater will be connected to the gas supply piping using an approved ½” x 24
stainless steel flexible gas connector (903000013) as supplied by the manufacturer of the
heater.
B. Mounting Options:
a. Standard: The heater is supplied with a top cover that facilitates mounting of the heater
using chain or rod
b. Wall Mount Bracket: Optional bracket (903000024) facilitates mounting of the heater to
a wall surface
c. Wall Mount Arm: Optional Mounting Arm assembly (903000028) extends the heater
location 30 inches from a wall or ceiling mounting surface
d. Post Mount Bracket: Optional Post Mount Bracket (903000026) facilitates mounting of
the heater on a 4 inch diameter post (post field supplied by others)
Copyright 2021 Rinnai America Corporation. Rinnai® is a registered trademark of Rinnai Corporation used
under license by Rinnai America Corporation. Rinnai America Corporation continually updates materials, and as
such, content is subject to change without notice.