Instructions / Assembly

14 Outdoor Conversion Manual
Complete the checklist in the Post-Water
Heater Installation Checklistsection of
the Tankless Water Heater Installation
and Operation Manualwhen installation is
complete.
For detailed information on installation and
operation information, refer to the
Tankless Water Heater Installation and
Operation Manual.
If "LPG" (Liquid Propane Gas) is selected,
apply the supplied gas conversion label at
an open space above the existing label on
the left side of the water heater.
Note: See the Key Points For A
Successful Installationdocument (on
tankless water heater front cover) for
illustration of label location.
The default altitude setting for this water
heater is 0-2,000 ft. (0-610 m). If this water
heater is installed at a different altitude,
select the appropriate altitude setting.
Also, set up other parameters properly.
Refer to the section Configure Parameter
Settingsin the Tankless Water Heater
Installation and Operation Manualfor
specific details on setting parameters.
The controller is automatically locked after 30
minutes of inactivity. To unlock the controller:
1. Press and hold down the Prioritybutton.
2. While holding down the Prioritybutton,
press the up arrow button until a beep is
heard (approximately 5 seconds). Then,
release both buttons at the same time.
Note: The key symbol on the controller will not
illuminate, indicating the controller is unlocked.
Priority
button
Up arrow
button
Key symbol
If the gas type is changed, you must power
cycle the water heater (turn off electrical power
to the water heater, then turn on power again).
Power can be turned off by unplugging the
power cord or turning off electricity at the circuit
breaker. The controller does not control the
electrical power to the water heater.
IMPORTANT
IMPORTANT